Sensata / Crydom A2 Series Solid State Relay, 75 A Load, Panel Mount, 280 Vrms Load, 280Vrms Control

Offre groupée disponible

Sous-total (1 unité)*

95,42 €

(TVA exclue)

115,46 €

(TVA incluse)

Add to Basket
sélectionner ou taper la quantité
Temporairement en rupture de stock
  • Expédition à partir du 25 mai 2026
Besoin de plus? Cliquez sur " Vérifier les dates de livraison " pour plus de détails
Unité
Prix par unité
1 - 495,42 €
5 - 990,64 €
10 - 2485,88 €
25 - 4981,11 €
50 +76,33 €

*Prix donné à titre indicatif

N° de stock RS:
291-2090
Référence fabricant:
A2475
Fabricant:
Sensata / Crydom
Recherchez des produits similaires en sélectionnant un ou plusieurs attributs.
Sélectionner tout

Marque

Sensata / Crydom

Product Type

Solid State Relay

Maximum Load Current

75A

Mount Type

Panel

Maximum Load Voltage

280Vrms

Minimum Load Voltage

280V

Maximum Control Voltage

280Vrms

Minimum Control Voltage

90V

Series

A2

Terminal Type

Screw

Switching Function

Zero Voltage Switching

Minimum Operating Temperature

-40°C

Maximum Operating Temperature

80°C

Length

58.4mm

Height

23mm

Width

22.6 mm

Standards/Approvals

RoHS

Off State Leakage Current

10mA

Output Type

SCR

Capacitance

8pF

Crydom Series 1 Solid State Relays


Crydom Series 1 range of solid state relays offer a wide range of ratings from 10 A to 125 A at 24 V ac to 280 V ac. Crydom has incorporated many features within this particular range of panel mount solid state relays including AC or DC control and SCR output for heavy industrial loads. Both zero-crossing (resistive loads) and random-fire (inductive loads) output versions are available.

Features and Benefits


600 V blocking capacity;SCR Output for heavy industrial loads;Internal snubber circuitry;Filter, cover and thermal pads available ;Terminal Type Screw; Saddle Clamp;Input-output Capacitance: 8 pF;Isolation Voltage 4 kVrms;Dimensions: H22.9 x D58.4 x W45.7mm

Crydom Solid State Relay and Accessories


Note

Heat sink not included. For load current de-rating and heat sink details see manufacturers datasheet

Approvals

UL recognised component for Canada and US, VDE

Caution

Derating will limit the maximum load current at temperatures above 25 °C