ifm electronic ClassicLine Series I/O Module, 4 Port, Bus System AS Interface

Sous-total (1 unité)*

163,16 €

(TVA exclue)

197,42 €

(TVA incluse)

Add to Basket
sélectionner ou taper la quantité
En stock
  • 6 unité(s) prête(s) à être expédiée(s) d'un autre centre de distribution
Besoin de plus? Cliquez sur " Vérifier les dates de livraison " pour plus de détails
Unité
Prix par unité
1 +163,16 €

*Prix donné à titre indicatif

N° de stock RS:
739-6765
Référence fabricant:
AC5208
Fabricant:
ifm electronic
Recherchez des produits similaires en sélectionnant un ou plusieurs attributs.
Sélectionner tout

Marque

ifm electronic

Product Type

I/O Module

Inlet Connection Type

ASi Flat Cable Connection

Number of Ports

4

Maximum Operating Voltage

50V

Series

ClassicLine

Interface Type

Bus System AS Interface

Housing Material

Polyamide

IP Rating

IP67

Minimum Operating Temperature

-25°C

Maximum Operating Temperature

70°C

Standards/Approvals

EMC EN 50295, IEC 61000-6-2

Output Type

Digital Output, Transistor PNP

Minimum Operating Voltage

26.5V

Pays d'origine :
DE

AS-I Module, Fast Mounting, 4 Outputs


AS-I flat cable connection

Sockets M12x1

Digital outputs, transistor, PNP

Addressing socket

Voltage range: 24Vdc

Three orientations of the flat cable are possible

Total current consumption from AS-I: <50mA

Electrically separated

Short circuit proof

Integrated watchdog

Actuator Sensor Interface (AS-I)


Actuator Sensor Interface, AS-I


AS-I is a method of providing communication from simple discrete components such as an inductive sensor or switching valve via a simple two-wire network to a controlling device such as a PLC or PC.

A unique feature of the AS-I system is the flat, two-core cable (stock no 242-6189) designed to enable fast and easy connection, ensuring correct polarity every time. The cable can be used in a network up to 100m (300m if repeaters are used).

By providing power and data down the same cable, the amount of time normally used to connect sensors and actuators is dramatically reduced, thereby providing savings in cable requirements and man-hours.

The choice of AS-I connection modules enables the user to connect standard sensors/actuators to the BUS with all the address benefits of using dedicated sensors/actuators. It also serves to increase the number of I/O nodes that are available to the user by the use of addressable splitter boxes. The connection modules are available in a variety of packages and can accommodate up to 4 inputs and 4 outputs. This enables up to 124 inputs and 124 outputs to be connected to a single AS-I network.

Another feature of AS-I system is the method by which the sensors or modules communicate with the host. The design of the communications protocol ensures high data accuracy and error detection capabilities, making the ASI system ideal for automation in noisy and industrial environments.

Benefits of AS-I


Replaces hard wiring

High data speed

Low cost installation

Intelligent diagnostics

Easy to learn and install

Highly flexible

Can connect to other fieldbus systems

User-friendly

Off-site pre-assembly and test

Easy maintenance

Faster on-site commissioning

Host or stand alone use

Able to use standard sensors and actuators (using modules)

Liens connexes