Fluke 1775/BASIC Power Quality Analyser, 3-Phase, 2000 A Max, 1000V dc

Sous-total (1 unité)*

9 024,00 €

(TVA exclue)

10 919,04 €

(TVA incluse)

Add to Basket
sélectionner ou taper la quantité
Stocké-e par le fabricant
  • Prêt à être expédié à partir du 16 novembre 2026
Besoin de plus? Cliquez sur " Vérifier les dates de livraison " pour plus de détails
Unité
Prix par unité
1 +9 024,00 €

*Prix donné à titre indicatif

N° de stock RS:
232-0534
Référence fabricant:
FLUKE-1775/BASIC
Fabricant:
Fluke
Recherchez des produits similaires en sélectionnant un ou plusieurs attributs.
Sélectionner tout

Marque

Fluke

Maximum Current Measurement

2000A

Product Type

Power Quality Analyser

Maximum Power Measurement

1500mW

Number of Phases

3

Voltage Accuracy

±0.1 %

Display Type

Touch Screen

Maximum Voltage Measurement

1000V dc

Measurement Type

Frequency, Voltage, Current

Measurement Standards

IEC 61010-2-30

Interface Type

Ethernet, USB

Memory Size

8GB

Minimum Operating Temperature

-10°C

Power Source

Battery

Maximum Operating Temperature

50°C

Length

280mm

Battery Type

Lithium-ion

Width

190mm

Standards/Approvals

IEEE 1459, IEC 61000-4-7, IEC 61000-4-15 Class F1, IEC 61000-4-30 Class A, IEC 62586 PQI-A-PI

Weight

2.1kg

Height

62mm

Model Number

1775/BASIC

Battery Life

1.5h

Maximum Frequency

69Hz

Minimum Frequency

42.5Hz

Pays d'origine :
RO

Fluke Power Quality Analyser, 1000V Maximum Voltage Measurement, 2000A Maximum Current Measurement - FLUKE-1775/BASIC


This power quality analyser is a handheld instrument for capturing and logging electrical system behaviour during installation, testing and fault diagnosis. It records voltage, current, frequency and power parameters across three phases and neutral, and is suitable for on-site studies where portability, touchscreen operation and Rapid data transfer are required.

Features & Benefits


• 1MHz transient sampling captures fast voltage spikes for root-cause analysis
• ±0.1% voltage accuracy supports precise diagnostic measurements
• 2000A measurement capability with compatible clamps for large conductors
• 1000V measurement range for service-entrance and downstream work
• 8GB internal memory with USB and Ethernet for quick data export
• Lithium‑ion battery operation provides 1.5 h runtime for field tasks

**Applications**


• Suitable for energy surveys and load testing in industrial plants
• Ideal for harmonic surveys and compliance comparison to standards
• Used for investigating nuisance circuit‑breaker tripping events
• Can be used for transient discovery causing equipment failures
• Suitable for field logging when powered from the measured circuit

How does it synchronise time for multi-site measurements?


It supports GPS timing and Network Time Protocol to achieve sub‑millisecond to millisecond synchronisation depending on method and connectivity.

What interfaces are available for data transfer in the field?


Data can be transferred via USB‑C, USB‑A, 1Gbit/s Ethernet, Wi‑Fi, Bluetooth or LTE where module options are fitted.

Which measurement bandwidths are available for harmonics and transients?


PQ measurements cover DC to 30 kHz for harmonics and up to 1 MHz bandwidth for transient capture with high‑speed sampling options.

How are current sensors connected and ranged automatically?


The analyser accepts Rogowski coils and clamp sensors with automatic range selection and scaling per attached accessory.

What environmental limits apply during operation?


It operates between −10°C and 50°C with defined humidity limits and an IP50 rating for typical industrial conditions.

Liens connexes