Siemens Condensation Detector

Sous-total (1 unité)*

129,28 €

(TVA exclue)

156,43 €

(TVA incluse)

Add to Basket
sélectionner ou taper la quantité
Temporairement en rupture de stock
  • Expédition à partir du 24 décembre 2025
Besoin de plus? Cliquez sur " Vérifier les dates de livraison " pour plus de détails
Unité
Prix par unité
1 +129,28 €

*Prix donné à titre indicatif

N° de stock RS:
287-8920
Référence fabricant:
QXA2100 / S55770-T375
Fabricant:
Siemens
Recherchez des produits similaires en sélectionnant un ou plusieurs attributs.
Sélectionner tout

Marque

Siemens

Device Type

Condensation Detector

Mounting Type

Surface Mount

Height

83mm

Length

60mm

Statut RoHS non applicable

Pays d'origine :
DE

Siemens Sensor, Surface Mount Type, 24V AC/DC Supply Voltage - QXA2100


This sensor is a condensation detector designed for surface mounting, measuring 83mm in height and 60mm in length. Ideal for monitoring condensation in environments with chilled ceilings and HVAC systems, it operates with a supply voltage of 24V AC/DC. Weighing only 0.126kg, this reliable device features an IP40 rating, making it suitable for various industrial applications.

Features & Benefits


• Accurately monitors humidity levels near the dew point
• Prevents condensation damage on chilled ceilings
• Functions as a condensation switch for HVAC systems
• Built with a flame-retardant thermoplastic housing
• Supports mounting on surfaces or via tensioning straps
• Quick response time stabilises operations under rising humidity

Applications


• Monitor condensation in buildings with HVAC systems
• Used for chilled ceiling to prevent moisture build-up
• Suitable for detection at critical points in air conditioning
• Effective in ventilation systems to mitigate condensation risk
• Ideal for mounting on pipes with diameters from 10mm to 100mm

How does the condensation detection technology function in this device?


The device operates by recording relative humidity close to the dew point. It activates the relay before reaching this point, allowing immediate adjustments to the cooling processes to prevent condensation.

What precautions should be taken when installing the sensor?


It is essential to mount the sensor in the coldest area of the surface it protects. Additionally, applying a thin layer of thermal conductive paste on the mounting surface enhances accuracy and performance.

What is the expected response time for humidity changes?


The sensor displays a maximum response time of 3 minutes when detecting humidity variations from 80% to 99% relative humidity. This quick action helps maintain optimal conditions in sensitive environments.