Siemens Room Temperature Sensor

Sous-total (1 unité)*

134,33 €

(TVA exclue)

162,54 €

(TVA incluse)

Add to Basket
sélectionner ou taper la quantité
En stock
  • Plus 2 unité(s) expédiée(s) à partir du 15 décembre 2025
Besoin de plus? Cliquez sur " Vérifier les dates de livraison " pour plus de détails
Unité
Prix par unité
1 +134,33 €

*Prix donné à titre indicatif

N° de stock RS:
287-8719
Référence fabricant:
QAA2061 / BPZ:QAA2061
Fabricant:
Siemens
Recherchez des produits similaires en sélectionnant un ou plusieurs attributs.
Sélectionner tout

Marque

Siemens

Device Type

Room Temperature Sensor

Mounting Type

Wall Mount

Height

100mm

Length

90mm

Statut RoHS non applicable

Pays d'origine :
CN

Siemens Sensor, 100mm Height, 24V Supply Voltage - QAA2061


This room temperature sensor is designed for efficient indoor climate control in various settings. With a wall mount design, it measures 100mm in height and 90mm in length and width. Operating on a voltage of 24V AC or a 5 to 35V DC, it provides accurate temperature readings up to 50°C. The sensor boasts a versatile screw termination type and is rated IP30 for protection against dust.

Features & Benefits


• Active sensing element ensures precise temperature acquisition
• Outputs temperature signals of DC 0...10V or 4...20mA
• High maximum operating temperature of +50°C for diverse environments
• Suitable for concealed or surface-mounted wiring options
• Designed for wall mounting to optimise space utilisation
• Designed for compatibility with HVAC systems for seamless integration

Applications


• Used in heating, ventilation, and air conditioning systems for precise monitoring
• Ideal for commercial spaces needing regular temperature assessments
• Effective in indoor environments where accurate climate control is critical
• Compatible with systems that accept DC signal outputs for temperature readings

What is the maximum distance allowed for cabling when installing the sensor?


The permissible lengths for copper cables are up to 50m for 0.6mm diameter, 150m for 1mm², and 300m for 1.5mm², ensuring flexibility in installation.

How does the sensor compensate for varying operating voltages?


It is specifically calibrated for an operating voltage of AC 24V or DC 24V to account for high power loss which may influence measurement accuracy across different voltages.

What mounting options are available with the sensor?


It is designed for wall mounting and can accommodate both concealed wiring from behind or surface-mounted wires using knock-out openings for flexible installation.

How do I select the measuring range on the device?


The sensor features a setting element accessible after removing the baseplate, allowing you to choose from multiple configurations including factory settings for various temperature

What should be considered when placing the sensor in a room?


It should be mounted away from direct sunlight, heat sources, and areas of airflow disruption, ensuring accurate readings for optimal performance in monitoring.