ABB S800N Miniature Circuit Breaker, 1-Pole, 32A, Type C, 400V ac AC, 690 V DC, 36 kA Breaking Capacity

Actuellement indisponible
Nous ne savons pas si cet article sera de nouveau disponible. RS a l'intention de le retirer de son assortiment sous peu.
N° de stock RS:
140-873
Référence fabricant:
2CCS891001R0324
Fabricant:
ABB
Recherchez des produits similaires en sélectionnant un ou plusieurs attributs.
Sélectionner tout

Marque

ABB

Number of Poles

1

Product Type

Miniature Circuit Breaker

Current Rating

32A

Tripping Characteristics

Type C

Rated AC Voltage

400V ac

Rated DC Voltage

690V

Mount Type

DIN Rail

Breaking Capacity

36kA

Series

S800N

Terminal Type

Screw

IP Rating

IP20, IP40

Depth

82.5mm

Height

95mm

Width

27mm

Standards/Approvals

IEC/EN 60898-1, IEC/EN 60947-2

Reset Actuator Type

I/O Actuator

Tripping Mechanism

Electromechanic, Thermal

Pays d'origine :
CH

ABB S800N Series Miniature Circuit Breaker, 32A Current, Type C Tripping Characteristics - 2CCS891001R0324


This miniature circuit breaker provides overcurrent protection for single-phase installations and is intended for DIN-rail mounting. It operates on alternating systems up to 400V AC and is also rated for DC applications up to 690V. The device combines thermal and electromechanical tripping to respond to both overloads and short-circuit conditions while offering selectable ingress protection levels for panel and enclosure use.

Features and Benefits:


• 36kA breaking capacity delivers robust short-circuit interruption
• 32A current rating supports moderate load distribution
• Type C tripping characteristic protects mainly against short-duration surges
• I/O reset actuator enables clear manual switching status
• Screw terminals provide secure conductor connection

Applications


• Ideal for protecting lighting and motor circuits with inrush currents
• Used with DIN-rail systems in modular electrical panels
• Can be used for AC and DC control circuits up to rated voltages

What pole configuration does it use?


It is configured as a single-pole device to interrupt one phase conductor.

How is the device mounted in an installation?


The unit mounts directly onto a standard DIN rail for tool-assisted installation.

Which standards define its electrical performance?


Performance aligns with IEC/EN 60898-1 and IEC/EN 60947-2 specifications.

What type of tripping mechanism responds to faults?


A combined thermal element for overloads and an electromechanical mechanism for Rapid fault clearance.

What ingress protection options are available?


It is supplied with ratings of IP20 and IP40 for different enclosure needs.